Products

JVP Raised Access Floors
Bathgate Access Floors
Panel Finishes

Vinyl - Comming Soon

 

JVP Light Grade Floors

 

C3TTL - Chipboard Core

jvp density•  High density chipboard core E1 class, 650 kg/m3, bonded with a moisture
curing adhesive into a patented double folded lock of fully encapsulated
0.5mm hot deep galvanized steel.
•  Panel dimensions: 600*600*23 mm / 8 kg.
• The dimensional tolerances ratedas per UNI EN 12825 at the highest Class 1.

jvp load baring•  Load baring Performances as per UNI EN 12825 stringerless at FFH 400mm
•  Point load at weakest point                                        > 2.55 kN
•  Ultimate load  with Safety Factor 3                            > 7.47 kN
•  Working load fixed deflection < 2.5 mm                     > 3.00 kN
•  RATED CLASS AS PER UNI EN 12825                2/3,0/A/1

jvp fire performance•  Fire Performance
•  Fire reaction EN 13501-1:                                   Class 1, Bfl-S1
•  Fire resistance EN 13501-2:                                 R.E.I. 30, R.E.90
•  Fire rate as per  PSAMOB:              Index i1, Class 1,Rating class 0

 

jvp noise attenuation•  Noise Attenuation EN 20140-9 & EN 20140 - 6:
•  Air bone noise as per ISO 717 - 1 Dn1f1w:                        > 42 dB
•  Impact noise as per ISO 717 - 2 Ln1w:                             < 68 dB

 

jvp proposed use•  Proposed for office and commercial use.
•  Used as working platform during construction. 
•  Water and reagents poof.


•  25 YEARS WARRANTY

Click here to download the C3TTL Datasheet

C4TTL - Chipboard Core

jvp density•  High density chipboard core E1 class, 650 kg/m3, bonded with a moisture
curing adhesive into a patented double folded lock of fully encapsulated
0.5mm hot deep galvanized steel.
•  Panel dimensions: 600*600*29 mm / 9 kg.
• The dimensional tolerances ratedas per UNI EN 12825 at the highest Class 1.

jvp load baring•  Load baring Performances as per UNI EN 12825 stringerless at FFH 400mm
•  Point load at weakest point                                       > 3.57 kN
•  Ultimate load  with Safety Factor 3                           > 8.01 kN
•  Working load fixed deflection < 2.5 mm                   > 3.50 kN
•  RATED CLASS AS PER UNI EN 12825              2/3,0/A/1

jvp fire performance•  Fire Performance
•  Fire reaction EN 13501-1:                                       Class 1, Bfl-S1
•  Fire resistance EN 13501-2:                                R.E.I. 30, R.E.90
•  Fire rate as per  PSAMOB:             Index i1, Class 1,Rating class 0

 

jvp noise attenuation•  Noise Attenuation EN 20140-9 & EN 20140 - 6:
•  Air bone noise as per ISO 717 - 1 Dn1f1w:                        > 42 dB
•  Impact noise as per ISO 717 - 2 Ln1w:                             < 68 dB

 

jvp proposed use•  Proposed for office and commercial use.
•  Used as working platform during construction. 
•  Water and reagents poof.

•  25 YEARS WARRANTY

Click here to download the C4TTL Datasheet

Additional Information

Light Grade (UK) PSA MOB PF2

Standard application for office space equipped with filing cabinets, standard office equipment with average density of personnel occupancy, without the need for application of heavy machinery and or archive storage, generally defined as normal use private office space without heavy volume of pedestrian foot traffic: it roughly corresponds to theClass 1 and 2 of EN 12825

Medium Grade (UK) PSA MOB PF2

Standard application for commercial office space equipped with filing cabinets, general office equipment with average density of occupancy including flexibility for the future changes in application. Normally used for private and public commercial offices, Banks, Retail Shops, Libraries, etc. Generally defined as heavy volume foot traffic circulation and medium machinery equipment and/or heavy filing/archive storage: it roughly corresponds to the Class 3 and 4 of EN 12825.

Heavy Grade (UK) PSA MOB PF2

Specific use of technical spaces like electrical cabinet, server room, telephone exchanger cabinets, industrial laboratory, light industrial production. Generally defined as space where the loading of machinery is and will be higher than general offices: it roughly corresponds to the Class 5 and 6 of EN 12825.

Extra Heavy Grade (UK) PSA MOB PF2

Normally used for heavy plant rooms and or particularly heavy machinery and or extreme heavy rolling loads (car showrooms).

EN 12825 does not have a classification corresponding with Extra Heavy Grade.

A further element considered by (UK) PSA MOB PF2 is Uniformly Distributed Load (UDL) capacity, which is not mentioned or considered by EN 12825.

In many countries the UDL is not considered as an important element to qualify a raised access floor performance, because the limit of the performance of a raised access floor is the performance of the concrete slab of the building, which is normally limited to the UDL range of 2 to 8 kN per square metre. This value is considerably lower than the load bearing capacity of a raised access floor light grade performance.